| 注册
首页|期刊导航|广东电力|GIS沿面放电缺陷的振动检测法分析

GIS沿面放电缺陷的振动检测法分析

刘勇业 马宏忠 姜宁 李凯 李勇 许洪华

广东电力2017,Vol.30Issue(3):71-75,80,6.
广东电力2017,Vol.30Issue(3):71-75,80,6.DOI:10.3969/j.issn.1007-290X.2017.03.014

GIS沿面放电缺陷的振动检测法分析

Analysis on Vibration Detection Method for Creeping Discharge Defect in GIS

刘勇业 1马宏忠 1姜宁 2李凯 2李勇 2许洪华2

作者信息

  • 1. 河海大学 能源与电气学院,江苏 南京 211100
  • 2. 国网江苏省电力公司南京供电公司,江苏 南京 210008
  • 折叠

摘要

Abstract

With regard to common but serious partial discharge (PD) defect such as insulation creeping discharge in gas insulated metal enclosed switchgear and controlgear (GIS), there are no proper diagnosis methods at present.Therefore, vibration method was adopted for fault monitoring and diagnosis.It was discovered that energy of GIS PD mainly concentrated in the range of 1.6~6.4 kHz frequency band according to wavelet packet analysis on collected GIS vibration signals.Thus, 1.6~6.4 kHz frequency band was proposed to be taken as the characteristic frequency band and PD characteristic coefficient was presented which was defined as ratio of the total energy of 1.6~6.4 kHz frequency band and that of 6.4~12.8 kHz frequency band.By observing the value of characteristic coefficient which was compared with that under the normal condition, it was able to judge whether there was creeping discharge defect in GIS.Threshold range of the characteristic coefficient was presented and severity degrees of creeping discharge were divided as well.Research indicates that this method can effectively diagnose creeping discharge fault in GIS and has better effect compared with other methods.

关键词

电力气体绝缘金属封闭开关设备(GIS)/绝缘子沿面放电/振动/特征频段/局部放电特征系数/阈值

Key words

gas insulated metal enclosed switchgear and controlgear/insulator creeping discharge/vibration/characteristic frequency band/partial discharge characteristic coefficient/threshold value

分类

信息技术与安全科学

引用本文复制引用

刘勇业,马宏忠,姜宁,李凯,李勇,许洪华..GIS沿面放电缺陷的振动检测法分析[J].广东电力,2017,30(3):71-75,80,6.

基金项目

国网江苏省电力公司重点科技项目(J2015054) (J2015054)

广东电力

OACSTPCD

1007-290X

访问量0
|
下载量0
段落导航相关论文