中国电力2017,Vol.50Issue(5):59-64,6.DOI:10.11930/j.issn.1004-9649.2017.05.059.06
1 000 kV特高压避雷器泄露电流异常缺陷分析
Comprehensive Analysis on Abnormal Defects of Leakage Current on 1 000 kV UHV Surge Arrester
高燃 1束畅 1蒲道杰 1尹建军 1朱雨晨 1黄道均 1吴大胜1
作者信息
- 1. 国网安徽省电力公司检修公司,安徽合肥230061
- 折叠
摘要
Abstract
According to the operation of the high voltage side lightning arrester of main transformer in a 1 000 kV UHV transformer substation,a comprehensive analysis was made on the abnormal leakage current in terms of the radial discharge of arrester porcelain insulator contamination,the interference of surface leakage current,the influence of voltage harmonics and the damp of valve elements.And effective measures were used to diagnose the fault.Finally,corresponding check and return treatment was made according to the diagnosis results,which proves the correctness of the diagnosis.The analysis and diagnosis in this paper can provide a reference for the service of UHV arresters.关键词
特高压/避雷器/泄漏电流/阻性电流/异常Key words
ultra high voltage (UHV)/surge arrester/leakage current/resistive current/abnormal分类
信息技术与安全科学引用本文复制引用
高燃,束畅,蒲道杰,尹建军,朱雨晨,黄道均,吴大胜..1 000 kV特高压避雷器泄露电流异常缺陷分析[J].中国电力,2017,50(5):59-64,6.