中国电力2017,Vol.50Issue(5):78-83,6.DOI:10.11930/j.issn.1004-9649.2017.05.078.06
非侵入式低压配电网短路事故检测及定位方法
Non-Intrusive Fault Detecting and Locating Method in Low-Voltage Distribution Network
摘要
Abstract
Non-intrusive load monitoring (NILM) is an advanced measuring technology which does not require intrusive construction into users and complicated communication channel.In this paper,the NILM technology is innovatively applied into short-circuit-fault detection and location.Firstly,based on the results of experimental and theoretical analysis,the criterion and the relevant setting process for short-circuit fault with the breaker protection is proposed.Secondly,the fault location algorithms under NILM architecture are presented,which contains three steps:primary locating method for distribution level,primary locating method for important branch based on power drop model,and accurate location method by reusing sub-metering data.Totally four single-phase short-circuit accidents are detected and located during the experiments,which effectively improves the safety level of power users and reduces the construction cost of monitoring system.关键词
非侵入/短路事故/检测/故障定位/低压配电网Key words
non-intrusive/short-circuit fault/detecting/fault locating/low voltage power network分类
信息技术与安全科学引用本文复制引用
王伟,于建成,姚程,霍现旭,田娜,刘建宇,姚勋..非侵入式低压配电网短路事故检测及定位方法[J].中国电力,2017,50(5):78-83,6.基金项目
国家自然科学基金资助项目(51207020) (51207020)
国家电网公司科技项目(SGTJDK00DWJS1500097)This work is supported by the National Natural Science Foundation of China (No.51207020) and the Science and Technology Foundation of State Grid Corporation of China (No.SGTJDK00DWJS1500097). (SGTJDK00DWJS1500097)