电工技术学报2017,Vol.32Issue(10):12-19,8.
多馈入直流输电系统换相失败边界条件
Boundary Conditions of Commutation Failure in Multi-Infeed HVDC Systems
摘要
Abstract
In multi-infeed HVDC systems, AC faults at the terminal will likely lead to concurrent commutation failures of multiple HVDC converters, eventually cause the blocking of multiple HVDC system. Therefore, it is important to explore the interaction of voltages at different inverter side AC nodes and identify boundary conditions of concurrent commutation failure. The expression of the multi-infeed interaction factor (MIIF) was derived considering the influence of the HVDC system by steady-state power flow equations at the receiving-end bus. Then, concurrent commutation failure interaction factor (CCFIF) was derived, according to the minimum extinction angle of the inverters and the change in the DC current after the fault. The boundary conditions of concurrent commutation failures were investigated by this CCFIF index. Finally, the simulation results on a modified CIGRE benchmark of dual-infeed HVDC test system demonstrate the accuracy of the boundary conditions of concurrent commutation failure.关键词
多馈入直流输电系统/同时换相失败/边界条件/多馈入交互作用因子/同时换相失败交互因子Key words
Multi-infeed HVDC transmission system/concurrent commutation failure/boundary conditions/multi-infeed interaction factor/concurrent commutation failure interaction factor分类