流体机械2017,Vol.45Issue(5):67-71,5.DOI:10.3969/j.issn.1005-0329.2017.05.015
风机盘管加新风系统运行节能分析
Energy Saving Operation Analysis of Fan-coil Fresh System
摘要
Abstract
To reduce the operating energy conservation of the public buildings air conditioning system,an office building fan-coil fresh air system in Nanjing is taken as the research object, optimize the multi operating mode of this building air conditioning system. On the basis of optimization, measures of peak load regulation were studied from three aspects finally: the per person amount of fresh air, air conditioning temperature, supplying air temperature of air conditioning. With the aid of energy consumption simulation software——DEST, analyze the multi-partition air conditioning operation-plan and peak load regulation measure, the analysis results show that the energy consumption of multi-partition air conditioning operation-plan could save 30.21% throughout a year, energy consumption could be saved 18.44% under peak load regulation measure, and they provide good solutions to dynamic demand response system for implementing the air-conditioning energy consumption peak shaving.关键词
风机盘管/调峰方案/节能优化/能耗模拟Key words
fan-coil/peak shaving plan/energy conservation optimization/energy consumption simulation分类
机械制造引用本文复制引用
朱培根,何轶敏,刘长俊,宋桦,孔维同..风机盘管加新风系统运行节能分析[J].流体机械,2017,45(5):67-71,5.基金项目
国家高技术研究发展计划项目(2015AA050401) (2015AA050401)