Considering the regulating performance of multiple reactive power sources, a reactive power and voltage coordinated control strategy which comprehensively utilizes the static var generator (SVG), photovoltaic inverters and capacitors is presented, with two control stages involved.The first stage is coordinated voltage control considering multiple reactive power sources, which maximizes the use of reactive power sources, so as to reduce switching frequency of capacitors, and quickly responds to the change in system reactive power, while maintaining voltage stability at the point of common coupling.The second stage consists in dynamic reactive power optimization control, through the replacement of dynamic reactive power (SVG) with static reactive power (capacitors), and fast reactive power (SVG) with slow reactive power (photovoltaic inverters).The SVG retains sufficient reactive margin, to make the power grid more capable of surmounting the problem of voltage collapse.Finally, the reactive power and voltage control strategy is applied in actual photovoltaic power stations to verify the strategy.

关键词

光伏电站/公共连接点/电压控制/无功补偿/协调控制

Key words

photovoltaic power station/point of common coupling/voltage control/reactive power compensation/coordinated control

引用本文复制引用

刘双,张建周,王汉林,柏嵩..考虑多无功源的光伏电站两阶段无功电压协调控制策略[J].电力系统自动化,2017,41(11):120-125,168,7.

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|
下载量0
段落导航相关论文