断路器三相不一致保护可靠性分析及二次回路改进

Reliability Analysis and Secondary Circuit Improvement of Three-phase Inconsistent Protection for Circuit Breaker

江知瀚 1马迎新 1高旭 1刘蔚 1杜丽艳1

作者信息

  • 1. 国网冀北电力有限公司,北京市 100053
  • 折叠

摘要

Abstract

The typical secondary circuit of three-phase inconsistent protection for a circuit breaker is described along with its influence on the safe operation of the power grid.Also, the action reliability of the protection circuit is analyzed.Based on the performance test results of the time relay for the three-phase inconsistent protection, the action time and the action voltage are thoroughly investigated.Then an improved secondary circuit of three-phase inconsistent protection is proposed to solve the incorrect operation problems of relay protection, which are caused by the relay failure, contactor failure, or action time migration of the time relay.Finally, several measures have also been proposed to enhance the maintenance of three-phase inconsistent protection.

关键词

断路器/三相不一致保护/可靠性分析/二次回路/时间继电器

Key words

circuit breaker/three-phase inconsistent protection/reliability analysis/secondary circuit/time relay