电机与控制应用2017,Vol.44Issue(5):108-115,127,9.
定子匝间短路故障下双馈风力发电机组高压穿越性能研究
High Voltage Ride Through Research of Doubly-Fed Induction Generator System Under Sator Winding Inter-Turn Short Circuit Faulty Condition
胡兰青 1孙丽玲1
作者信息
- 1. 华北电力大学电气与电子工程学院,河北保定071003
- 折叠
摘要
Abstract
In order to study the effect of high voltage ride through (HVRT) of doubly-fed wind power system under sator winding inter-turn short circuit (SWITSC) faulty condition,based on the multi loop theory,a simulation mode of doubly fed induction generator under SWITSC faulty condition was established,the S-function in the MATLAB/Simulink was established.On the basis of fault loop characteristics,mathematical model of DFIG wind turbine on ABC coordinate system and dq0 coordinate system were established under normal and fault condition,and the electromagnetic characteristics was analyzed briefly under SWITSC fault,then the capability of high voltage ride through of DFIG was analyzed,the reason and the transient process of wind farm voltage rise were analyzed.The standard of high voltage ride through was provided.Focused on the simulation results of HVRT of DFIG under SWTTSC faulty condition,the explanation was given.The results showed that SWITSC faulty destroyed capability of HVRT of DFIG to a great extent.关键词
双馈感应发电机/定子绕组匝间短路/高压穿越/仿真Key words
doubly-fed induction generator (DFIG)/stator winding inter-turn short circuit (SWITSC)/high voltage ride through (HVRT)/simulation分类
信息技术与安全科学引用本文复制引用
胡兰青,孙丽玲..定子匝间短路故障下双馈风力发电机组高压穿越性能研究[J].电机与控制应用,2017,44(5):108-115,127,9.