容性设备相对介质损耗因数及电容量比值带电测试方法探析

王烨 杨晓国

电器与能效管理技术Issue(10):66-69,4.
电器与能效管理技术Issue(10):66-69,4.DOI:10.16628/j.cnki.2095-8188.2017.10.015

容性设备相对介质损耗因数及电容量比值带电测试方法探析

Discussion on the Method of Measuring the Dielectric Loss Factor and Capacitance Ratio of Capacitive Equipment

王烨 1杨晓国1

作者信息

  • 1. 国网运城供电公司,山西 运城 044000
  • 折叠

摘要

Abstract

In order to explore the capacitive equipment relative dielectric loss factor and capacitance ratio live test method,taking a 220 kV substation current transformer relative dielectric loss capacitance live detection problem as an example, through the unit current transformer live detection,the phase oil chromatography test,and the phase current transformer partial discharge test method,it can realize the live measurement of dielectric loss and capacitance.Under the premise of not affecting the reliability of the power supply, the method can not only obtain the latest status of the sample at any time,but also realistically reflect the insulation condition of the equipment in the running state.

关键词

介质损耗/带电测试/油色谱试验/绝缘

Key words

dielectric loss/live test/oil chromatographic test/insulation