Abstract
The DC component of short-circuit current in high power test affects di/dt and TRV at zero crossing point,and the quality and efficiency of the test depend on accurate control of the DC component.In the high power test,three separate switches are used for phase-selection closing to obtain the required short-circuit current.In this paper,the phase selection methods for respectively generating the fully symmetrical and the maximum asymmetrical short-circuit current are obtained through theory analysis,and the method for setting closing time series according to current waveform is summarized.Besides,a circuit containing Y/△ transformer is analyzed.关键词
短路电流/合闸开关/选相/对称/非对称Key words
short-circuit current/making switch/phase selection/symmetrical current/asymmetrical current引用本文复制引用
张晋波,者永祥,刘浩军,董玮,陈小柯..合闸开关选相对容量试验的影响研究[J].高压电器,2017,53(6):124-128,5.