| 注册
首页|期刊导航|高电压技术|消弧线圈接地系统同母多回线相继故障分析

消弧线圈接地系统同母多回线相继故障分析

吴争荣 蔡颖倩 张俊潇 董旭柱 王钢 刘志文

高电压技术2017,Vol.43Issue(7):2402-2409,8.
高电压技术2017,Vol.43Issue(7):2402-2409,8.DOI:10.13336/j.1003-6520.hve.20170628039

消弧线圈接地系统同母多回线相继故障分析

Fault Analysis on Successive Fault of Multi-feeders Connected to the Same Bus in Resonant Grounding System

吴争荣 1蔡颖倩 2张俊潇 3董旭柱 1王钢 2刘志文1

作者信息

  • 1. 南方电网科学研究院有限责任公司,广州510080
  • 2. 华南理工大学电力学院,广州510640
  • 3. 广东电网发展研究院有限责任公司,广州510080
  • 折叠

摘要

Abstract

Successive faults occur frequently at multi-feeder connected to the same bus in urban distribution networks,which is particularly severe in resonant grounding systems.To find out the cause of such accidents,we firstly studied steady-state overvoltage caused by single-phase-to-ground fault,and analyzed the influences of fault resistor and reactive power compensation on the steady-state overvoltage of healthy phases.Then,we analyzed the distribution characteristics of transient overvoltage caused by intermittent earth fault.The results show that the intermittent arc overvoltage at the end of a non-fault line is much higher than that of the faulty line.Thereby,phase-to-phase fault may occur first in a non-fault line.Therefore,taking an actual accident as an example,we used a simulation case in PSCAD/EMTDC to study the process of the accident.Combined with the fault information,the cause of the accident was revealed.At last,corresponding solutions were put forward.

关键词

相继故障/间歇性接地/工频过电压/弧光过电压/消弧线圈接地系统

Key words

successive faults/intermittent earth fault/power-frequency overvoltage/arcing overvoltage/resonant grounding system

引用本文复制引用

吴争荣,蔡颖倩,张俊潇,董旭柱,王钢,刘志文..消弧线圈接地系统同母多回线相继故障分析[J].高电压技术,2017,43(7):2402-2409,8.

基金项目

国家自然科学基金(51477057) (51477057)

中国南方电网公司科技项目(WYKJ00000020).Project supported by National Natural Science Foundation of China (51477057),Science and Technology Project of China Southern Power Grid Co.,Ltd.(WYKJ00000020). (WYKJ00000020)