一种基于直流内阻的电池组连接可靠性的检测方法

韩冰海 王东梅 李世云

电源技术2017,Vol.41Issue(7):981-983,3.
电源技术2017,Vol.41Issue(7):981-983,3.

一种基于直流内阻的电池组连接可靠性的检测方法

Research on battery connection reliability based on DC internal resistance

韩冰海 1王东梅 1李世云1

作者信息

  • 1. 中航锂电(洛阳)有限公司,河南洛阳471000
  • 折叠

摘要

Abstract

Battery DC internal resistance (DCIR) includes the resistance of cell itself and the contact resistance of connecting position after serial and parallel connection.Battery's DC internal resistance can rise if it connects unwell.Based on the DCIR of cell,the deviation of DCIR (ΔR) as the test index of battery connection reliability was proposed.Considering the shortcoming of ΔR in operation and fault recognition,another index instead of ΔR was proposed.It was the voltage difference of battery at the end of one minute discharge process with 1 C current,when the battery pack at 30%~60% SOC.It could be defined as ΔU.The passing standard of ΔU was provided.The test results show that ΔU is almost equal to the product of ΔR and current.So ΔU can be used as the test index of battery connection reliability and it increase more obviously than ΔR when any position connects unwell in the battery.According to the passing standard of ΔU,it can identify the unwell connection situation effectively and quickly.

关键词

电池组/螺栓连接/直流内阻/可靠性检测

Key words

batteries/bolt connection/DC internal resistance/reliability test

分类

信息技术与安全科学

引用本文复制引用

韩冰海,王东梅,李世云..一种基于直流内阻的电池组连接可靠性的检测方法[J].电源技术,2017,41(7):981-983,3.