广东电力2017,Vol.30Issue(7):65-69,5.DOI:10.3969/j.issn.1007-290X.2017.07.012
基于实时测量数据的电缆稳态载流量计算
Calculation on Steady-state Ampacity of Cable Based on Real-time Measured Data
摘要
Abstract
It is critical for realizing dynamic capacity-increase of the cable by accurately calculating ampacity of the cable.In order to correctly assess steady-state ampacity of the cable under different operational conditions, a steady-state thermal circuit model based on real-time measured data was built to solve real-time steady-state ampacity of the cable, and experiment on steady-state temperature rise was designed to verify reliability of this model.Comparison between experimental result and calculated result indicates that the calculated errors of real-time steady-state ampacity of the cable under different steady-state conditions are all negative and the absolute values of errors are less than 5%.Accuracy of the calculated result can meet requirements for engineering application.关键词
高压电缆/实时稳态载流量/稳态热路/外部环境/动态增容Key words
high voltage cable/real-time steady-state ampacity/steady-state thermal circuit/external environment/dynamic capacity-increase分类
信息技术与安全科学引用本文复制引用
徐涛,叶晓君,徐研,王鹏宇,林堂正,吴卓伦..基于实时测量数据的电缆稳态载流量计算[J].广东电力,2017,30(7):65-69,5.基金项目