地震地磁观测与研究2017,Vol.38Issue(3):93-99,7.DOI:10.3969/j.issn.1003-3246.2017.03.016
深井电极交叉供电对自然电位的影响
The effects of cross-power supply of the electrodes on spontaneous potential in deep wells
摘要
Abstract
At first, through the experimental demonstration, the reason of the spontaneous potential distortion in the Pingliang deep well resistivity observation is caused by the cross-power supply of the electrodes. Secondly, the effects of different electrodes powered on spontaneous potential were discussed. The results show that the power supply on measure electrodes will affect the spontaneous potential, but will not affect the resistivity measurement; The effects of unipolar electrode powered on spontaneous potentials are step jump, and recovers exponentially. The recovery time is of 10 hours or so. The peak of interference related to the supply current, power supply time and so on; Finally, The correction of the observed data has achieved good results.关键词
深井/地电阻率/自然电位/交叉供电/校正Key words
deep well/geo-electric resistivity/spontaneous potential/cross-power supply/correction引用本文复制引用
赵斐,叶青,张远富..深井电极交叉供电对自然电位的影响[J].地震地磁观测与研究,2017,38(3):93-99,7.基金项目
由中国地震局专项(项目编号:17A32ZX208) (项目编号:17A32ZX208)
中国地震局监测、预测、科研三结合课题(项目编号:162807) (项目编号:162807)