高压电器2017,Vol.53Issue(8):38-42,5.DOI:10.13296/j.1001-1609.hva.2017.08.007
1000kV特高压中性点电抗器匝间绝缘性能研究
Turn Insulation Performance of Neutral Reactor Under 1 000 kV UHV Alternating Current
李予全 1寇晓适 1郑含博 1王伟 1邵颖彪 1马伦 1李晓纲 1郭磊 1谢伟1
作者信息
- 1. 国网河南省电力公司电力科学研究院,郑州450052
- 折叠
摘要
Abstract
To understand the insulation property of neutral reactor in 1 000 kV UHV AC transmission project,the power frequency overvoltage was analyzed and the debugging data of the project were use to simulate the potential distribution of the neutral reactor under impulse voltage.Then,an on-site withstand voltage test method of turn insulation of neutral reactor was proposed,the dynamic stability and thermal stability of the neutral reactor in test process were calculated and checked,and the feasibility and applicability of the on-site withstand voltage test of turn insulation were proved theoretically.In addition,the proposed test method was verified in practical application.This test method is expected to be applied to hand over test of neutral reactor.关键词
交流特高压/中性点电抗器/匝间绝缘/动稳定性/热稳定性Key words
ultra-high voltage AC/neutral reactor/turn insulation/dynamic stability/thermal stability引用本文复制引用
李予全,寇晓适,郑含博,王伟,邵颖彪,马伦,李晓纲,郭磊,谢伟..1000kV特高压中性点电抗器匝间绝缘性能研究[J].高压电器,2017,53(8):38-42,5.