| 注册
首页|期刊导航|高压电器|±800kV天中特高压直流送端系统安全稳定性分析

±800kV天中特高压直流送端系统安全稳定性分析

巩晓玲 樊艳芳 钟显 郑少鹏 常喜强

高压电器2017,Vol.53Issue(8):43-48,54,7.
高压电器2017,Vol.53Issue(8):43-48,54,7.DOI:10.13296/j.1001-1609.hva.2017.08.008

±800kV天中特高压直流送端系统安全稳定性分析

Analysis on Security and Stability of ±800 kV Tianzhong UHVDC Sending Grid

巩晓玲 1樊艳芳 1钟显 1郑少鹏 2常喜强3

作者信息

  • 1. 新疆大学电气工程学院,乌鲁木齐830047
  • 2. 国网新疆电力科学研究院,乌鲁木齐830011
  • 3. 国网新疆电力调度控制中心,乌鲁木齐830002
  • 折叠

摘要

Abstract

In order to analyze the security and stability of Tianzhong UHVDC sending grid,this paper analyzes the influence of different DC operating conditions based on effective short circuit ratio (OESCR),filter switching and DC single (double)pole lock failure.Then analyzes the impact of frequency adjuster which is at Xinjiang grid on system frequency characteristic;And the influence on UHVDC stability when generator cutting or DC pole blocking faults under the DC isolated operation.The study results show that the operating conditions of the 6 or 8 generators of the DC auxiliary power station can be set up,and the frequency of DC operation is large affected by the frequency adjuster of power grid.But,the DC isolated system frequency stability and transient overvoltage problems are easy to be caused by the DC generator cutting and DC single pole lock failure when considering non control measures.Therefore,it should take stability control strategies or DC power emergency control to enhance the security and stability of the UHVDC system.

关键词

特高压直流/安全稳定/送端系统/运行工况/孤网

Key words

UHVDC/security and stability/sending grid/operating condition/island system

引用本文复制引用

巩晓玲,樊艳芳,钟显,郑少鹏,常喜强..±800kV天中特高压直流送端系统安全稳定性分析[J].高压电器,2017,53(8):43-48,54,7.

基金项目

国家自然科学基金项目(51467019).Project Supported by National Natural Science Foundation of China (NSFC)(51467019). (51467019)

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量5
|
下载量0
段落导航相关论文