| 注册
首页|期刊导航|电力系统自动化|基于路径描述的馈线分区N-1可装容量计算方法

基于路径描述的馈线分区N-1可装容量计算方法

孙明 董树锋 夏圣峰 吴浩

电力系统自动化2017,Vol.41Issue(16):123-129,7.
电力系统自动化2017,Vol.41Issue(16):123-129,7.DOI:10.7500/AEPS20161101003

基于路径描述的馈线分区N-1可装容量计算方法

Path Description Based Calculation Method for Available Capacity of Feeder Partition Satisfied with N-1 Security Criterion

孙明 1董树锋 1夏圣峰 2吴浩1

作者信息

  • 1. 浙江大学电气工程学院,浙江省杭州市310027
  • 2. 国网福建省电力有限公司福州供电公司,福建省福州市350009
  • 折叠

摘要

Abstract

Evaluation of feeder capacity is an important means to guaranteeing reliable operation of feeder.A method is proposed to calculate the available capacity of feeder partition satisfied with N-1 security criterion.Firstly,distribution networks at the same voltage level are divided into feeder partitions with automatic/manual switching devices as the boundary,which can be regarded as load nodes.The topology of the distribution network is described by all load nodes and all sets of power supply paths associated with load nodes.Taking path states as variables,the 0-1 linear programming model is developed to analyze N-1 security verification of feeders.To meet the practical marketing demand of the power supply company,by taking path states and the available capacity of feeder partition as variables,the mixed integer linear programming model is proposed to calculate the available capacity of feeder partition satisfied with N-1 security criterion.Finally,the calculation results of a practical 10 kV feeder group in a provincial capital show that the proposed method is practicable and effective.

关键词

供电路径/N-1安全校验/线性规划/可装容量

Key words

power supply path/N-1 security verification/linear programming/available capacity

引用本文复制引用

孙明,董树锋,夏圣峰,吴浩..基于路径描述的馈线分区N-1可装容量计算方法[J].电力系统自动化,2017,41(16):123-129,7.

基金项目

国家高技术研究发展计划(863计划)资助项目(2014AA051901).This work is supported by National High Technology Research and Development Program of China (863 Program) (No.2014AA051901). (863计划)

电力系统自动化

OA北大核心CSCDCSTPCD

1000-1026

访问量0
|