发电机短路试验中转子接地保护误动作分析及关键问题探讨

向方伟

水力发电2017,Vol.43Issue(9):73-76,4.
水力发电2017,Vol.43Issue(9):73-76,4.

发电机短路试验中转子接地保护误动作分析及关键问题探讨

Misoperation Analysis and Discussion on Key Problems of Rotor Grounding Protection in Generator Short-circuit Test

向方伟1

作者信息

  • 1. 水电水利规划设计总院,北京100120
  • 折叠

摘要

Abstract

In view of the misoperation of rotor one-point grounding protection in short-circuit test of self-excited shunt hydrogenerating set,the theoretic analysis on the principles of excitation system and relay protection are carried out and the operating characteristics of transformer and the influences of high harmonic are investigated.Through field test and recording voltage waveform,the reasons of protection malfunction are found out and corresponding treatment measures are put forward.On this basis,the key problems and precautions in short-circuit test of hydro-generator are also discussed.

关键词

发电机短路试验/转子接地保护/误动作

Key words

generator short-circuit test/rotor grounding protection/misoperation