一起220 kV瓷柱式断路器慢合故障及分析

赵现平 马宏明 程志万 白双全 张恭源 彭晶 彭兆裕

高压电器2017,Vol.53Issue(9):234-239,246,7.
高压电器2017,Vol.53Issue(9):234-239,246,7.DOI:10.13296/j.1001-1609.hva.2017.09.040

一起220 kV瓷柱式断路器慢合故障及分析

Analysis on a Slow-closing Accident of 220 kV Porcelain Column Type Circuit Breaker

赵现平 1马宏明 1程志万 1白双全 2张恭源 3彭晶 1彭兆裕1

作者信息

  • 1. 云南电网有限责任公司电力科学研究院,昆明650217
  • 2. 云南电网有限责任公司昆明供电局,昆明650217
  • 3. 云南电网公司,昆明650217
  • 折叠

摘要

Abstract

A slow-closing accident of 220 kV porcelain column circuit breaker was analyzed by means of on-site check,test,and disassembly inspection in the manufacturer.It was found that the fit tolerances are too small among the guide sleeve base,the guide sleeve and the guide rod of the circuit breaker,and the temperature compensation coefficients of the guide sleeve and guide rod are different due to their different materials.All these factors increased the closing resistance of the circuit breaker at high environmental temperature,and eventually leaded to this accident.In addition,countermeasures are suggested in this paper.

关键词

瓷柱式/断路器/导向套/慢合/慢分

Key words

porcelain column type/circuit breaker/guide sleeve/slow-closing/slow-opening