电测与仪表2017,Vol.54Issue(19):21-26,6.
基于立体九域图的变电站无功电压控制策略研究
Research on reactive voltage control strategy of substations based on space nine-domain diagram
张少雄 1王庆斌 1杨舒婷 2王承民 2黄辉 1刘涌3
作者信息
- 1. 广东电网有限责任公司云浮供电局,广东云浮527300
- 2. 上海交通大学,上海200240
- 3. 上海博英信息科技有限公司,上海200240
- 折叠
摘要
Abstract
Voltage qualified and reactive power is the basic condition for the safe and stable operation of power sys -tem.It is important to determine the appropriate reactive power compensation method and voltage regulation scheme for power network operation .Compared with the traditional nine-domain graph control strategy , the reactive power voltage control strategy based on the three-dimensional nine-domain diagram is proposed in this paper .The time axis is added while the upper and lower limits of the voltage in different time zones ( time zones ) are changing .Based on the global reactive power optimization model of load forecasting , the expected adjustment scheme of each substation in the distribution network is obtained , which divides the day into several time zones and obtains the operating boundary of each time zone according to the optimization curve .The reactive power and voltage control strategy of substation based on three-dimensional nine-domain diagram combines the merits of dynamic reactive power optimization and real-time control, which not only avoids the frequent adjustment of reactive power compensation equipment and main trans -former tap , but also improves the economic operation of substation .关键词
立体九域图/无功补偿/电压调节/控制策略Key words
space nine-domain diagram/reactive power compensation/voltage regulation/control strategy分类
信息技术与安全科学引用本文复制引用
张少雄,王庆斌,杨舒婷,王承民,黄辉,刘涌..基于立体九域图的变电站无功电压控制策略研究[J].电测与仪表,2017,54(19):21-26,6.