| 注册
首页|期刊导航|高电压技术|±1100kV特高压换流站支柱绝缘子屏蔽球参数优化设计

±1100kV特高压换流站支柱绝缘子屏蔽球参数优化设计

陈东 乐波 郭贤珊 付颖 金硕 田雨

高电压技术2017,Vol.43Issue(10):3189-3197,9.
高电压技术2017,Vol.43Issue(10):3189-3197,9.DOI:10.13336/j.1003-6520.hve.20170925007

±1100kV特高压换流站支柱绝缘子屏蔽球参数优化设计

Optimal Design of Shielding Ball Parameters for Post Insulator of ±1100 kV UHV Converter Station

陈东 1乐波 1郭贤珊 2付颖 2金硕 3田雨3

作者信息

  • 1. 国网北京经济技术研究院,北京102209
  • 2. 国家电网公司直流部,北京100031
  • 3. 武汉大学电气工程学院,武汉430072
  • 折叠

摘要

Abstract

Shielding fitting is an integral part of UHV converter station,and its surface electric field control is of vital importance to the normal operation of the converter station equipment.In order to achieve the surface electric field control of the shielding fittings of post insulators in ±1 100 kV converter station,taking the shielding balls of post insulators as the object,we established a fimite element model of 3D,and used the electrostatic field instead of the transient field to obtain the surface electric field distribution of the shielding fittings under the switching impulse overvoltage.Moreover,we discussed the effects of shape of the shielding balls,size of the hole chamfer,depth and angle chamfer of the hole,and other factors on the fittings surface electric field distribution under impulse voltage.The results showed that,under the impulse voltage,the maximum surface electric field intensity of the design scheme of ‘drum'fitting can be controlled under 21 kV/cm,the safety margin is large.The shielding balls with radius of the hole chamfer above 100 mm can effectively reduce the electric field intensity.In addition,reducing the opening depth or the inclination angle is also beneficial to controlling the electric field intensity.The research results can provide some references for the design and installation of the shielding balls of±l 100 kV UHV converter station.

关键词

±1100 kV特高压换流站/屏蔽金具/支柱绝缘子/电场分布/电位分布/有限元法

Key words

±1100 kV UHV converter station/shielding fittings/post insulators/electric field distribution/potential distribution/FEM

引用本文复制引用

陈东,乐波,郭贤珊,付颖,金硕,田雨..±1100kV特高压换流站支柱绝缘子屏蔽球参数优化设计[J].高电压技术,2017,43(10):3189-3197,9.

基金项目

国家重点研发计划(2016YFB0900805).Project supported by National Key Research and Development Program (2016YFB0900805). (2016YFB0900805)