电网技术2017,Vol.41Issue(11):3405-3413,9.DOI:10.13335/j.1000-3673.pst.2017.1922
±1100kV直流输电线路带电作业屏蔽防护研究
Research on Shield Protection for Hot-Line Work on±1100kV DC Transmission Line
摘要
Abstract
As the highest DC transmission voltage level over the world,±1100kV DC transmission line will be built in China soon. Electric field strength in surrounding space of ±1100kV DC line is much stronger than that of±800kV and lower voltage level line. To ensure safety of hot-line work on ±1100kV DC lines, its safety protection should be researched. Firstly, based on proposed screening clothes, test results of hot-line work shield protection on±1100kV DC line were given, including measurements of characteristics of screening clothes, their inside and outside electrical field strengths, flowing through current of hot-line work screening clothes, discharge arc current and audible noise. Then, safety control level of±1100kV DC hot-line work shield protection was analyzed. Finally, based on the test results, precautions for shielding protection in± 1100kV hot-line work were summarized. The results show that it is feasible to hot-line work on± 1100kV DC transmission lines with high quality screening clothes.关键词
±1100kV直流输电线路/带电作业/屏蔽服/安全防护/电场强度/可听噪声/电位转移电流Key words
±1100kV DC transmission line/hot-line work/screening clothes/shield protection/field strength of body surface/audible noise/discharge arc current分类
信息技术与安全科学引用本文复制引用
张福轩,姚修远,石生智,丁健康,李金迪,丁玉剑,高海峰..±1100kV直流输电线路带电作业屏蔽防护研究[J].电网技术,2017,41(11):3405-3413,9.基金项目
国家重点研发计划项目(2016YFB0900802). Project Supported by National Key Research and Development Program (2016YFB0900802). (2016YFB0900802)