| 注册
首页|期刊导航|高电压技术|柔性直流输电系统电缆护套过电压仿真

柔性直流输电系统电缆护套过电压仿真

孙毅 张轶 贺之渊 尚康良

高电压技术2017,Vol.43Issue(11):3528-3533,6.
高电压技术2017,Vol.43Issue(11):3528-3533,6.DOI:10.13336/j.1003-6520.hve.20171031006

柔性直流输电系统电缆护套过电压仿真

Simulation of Cable Sheath Over-voltage in VSC-HVDC System

孙毅 1张轶 1贺之渊 2尚康良3

作者信息

  • 1. 华北电力大学电气与电子工程学院,北京102206
  • 2. 全球能源互联网研究院先进输电技术国家重点实验室,北京102209
  • 3. 全球能源互联网研究院直流电网技术与仿真北京市重点实验室,北京102209
  • 折叠

摘要

Abstract

Reliability of DC cable is the key factor to ensure the voltage-sourced converter-based high voltage direct current (VSC-HVDC) transmission,so analysis of cable body fault will provide basis for designing DC cables as well as protecting transmission lines in VSC-HVDC system.We established a γ-type underground cable model with distributed RLC parameters based on π-type underground cable model with distributed parameters.Meanwhile,Xiamen VSC-HVDC demonstrating project was applied to Matlab/Simulink for the fault characteristics of underground cable system when main insulation faulted.The simulation results show that fault current and induced voltage in sheath are both related to fault place of the main insulation,and the peak values of fault current increase as the fault point becomes closer to one side of the converter station,meanwhile,distributed induced voltages in metal sheath at both fault side and converter side of the DC cable increase as well.Besides,after the main insulation fault occurs at different distances from converter station,the induced overvoltage distribution trend of each unit in single-end grounding system is similar to that of the double-end grounding system,and the induced voltage value in the metal sheath can be hundreds to thousands of Volt.The model of sheath grounding with single-end can be used to analyze the fault characteristics of double-end grounded system approximately.

关键词

VSC-HVDC/直流电缆/绝缘故障/故障特性/过电压

Key words

VSC-HVDC/DC cable/insulation fault/fault characteristics/over-voltage

引用本文复制引用

孙毅,张轶,贺之渊,尚康良..柔性直流输电系统电缆护套过电压仿真[J].高电压技术,2017,43(11):3528-3533,6.

基金项目

国家重点研发计划(2016YFB0900700) (2016YFB0900700)

国家电网公司科技项目(±500 kV柔性直流海缆关键技术研究:直流电缆附件制备关键技术研究).Project supported by National Key Research and Development Plan (2016YFB0900700),Science and Technology Project of SGCC(Research on Key Technologies for ±500 kV Direct Current Cable:Research on Key Technologies for the Preparation of DC Cable Accessories). (±500 kV柔性直流海缆关键技术研究:直流电缆附件制备关键技术研究)

高电压技术

OA北大核心CSCDCSTPCD

1003-6520

访问量0
|
下载量0
段落导航相关论文