净水技术2017,Vol.36Issue(10):70-74,84,6.DOI:10.15890/j.cnki.jsjs.2017.10.012
供水系统中的余氯与TOC、CODMn及菌落总数之间的关系
Relationship between Residual Chlorine and TOC, CODMn & Colony Count in Water Supply System
万巧玲 1王良超1
作者信息
- 1. 国家城市供水水质监测网重庆监测站,重庆400013
- 折叠
摘要
Abstract
In order to systematically study the variation of residual chlorine in the water supply network under different temperatures,the finished water from a water plant in Chongqing City had being respectively monitored under 10,15,24 ℃ and 30 ℃ in four seasons.It was found that residual chlorine decay coefficients were so different because of various temperatures:K3o℃ > K24℃ > K15℃ > K10℃.The relationship between residual chlorine and TOC,CODMn,colony count under different temperatures and raw water qualities on every season was studied.It was practicable to change and adjust chlorine dosage in water plant based on the actual hydraulic retention time and different temperatures,which could save the costs of chlorine dosage and reduce the risks of drinking water because of the faster decay of residual chlorine by the higher temperature.关键词
余氯/总有机碳/高锰酸盐指数/菌落总数Key words
residual chlorine/TOC/CODMn/colony count分类
建筑与水利引用本文复制引用
万巧玲,王良超..供水系统中的余氯与TOC、CODMn及菌落总数之间的关系[J].净水技术,2017,36(10):70-74,84,6.