化工进展2017,Vol.36Issue(z1):92-100,9.DOI:10.16085/j.issn.1000-6613.2016-2232
LiCl溶液除湿系统的试验研究
Experimental investigation on LiCl liquid desiccant air dehumidification system
侯小兵 1邹同华 1韩雨松1
作者信息
- 1. 天津商业大学,天津市制冷技术重点实验室,天津 300134
- 折叠
摘要
Abstract
The liquid desiccant air handing device,which can be utilized without the restriction of climatic and geographical regions,is one of the most likely air-conditioning technologies to be promoted in large-scale application.In this paper,the single-stage LiCl solution desiccant process of countercurrent packing is studied through experiments.For the desiccant process,influence of the temperature (30—36℃) and relative humidity (50%—70%) of the inlet air on the dehumidification process is investigated.It is resulted that dehumidifying performance is enhanced with the increase of the temperature or relative humidity of the inlet air.In addition,for the solution regeneration process,the effect of inlet temperature of the regeneration air and solution on the regeneration process is studied.It is shown that,the rise of either temperature can increase the regeneration ability,but the effect from the temperature of the regeneration solution is stronger.However, the outlet temperature of the regenerated solution is also increased accordingly,which can lead to a larger amount of cooling load.关键词
溶液除湿/除湿性能/溶液再生Key words
liquid desiccant/dehumidifying performance/solution regeneration分类
化学化工引用本文复制引用
侯小兵,邹同华,韩雨松..LiCl溶液除湿系统的试验研究[J].化工进展,2017,36(z1):92-100,9.