理化检验-物理分册2017,Vol.53Issue(11):826-828,3.DOI:10.11973/lhjy-wl201711014
钢筋混凝土电杆断裂原因分析
Reason Analysis on Fracture of Reinforced Concrete Poles
熊亮 1万克洋 2刘蛟蛟 1曹智2
作者信息
- 1. 国网湖南省电力公司电力科学研究院,长沙 410007
- 2. 湖南省湘电锅炉压力容器检验中心有限公司,长沙 410004
- 折叠
摘要
Abstract
Two reinforced concrete poles in one substation fractured and collapsed suddenly,causing damage to the transformer and related equipments.Fracture reasons of reinforced concrete poles were analyzed by macro observation,measurement of cobblestone diameter and dimension of spiral steel bars, weigh measurement, mechanical property testing,chemical composition analysis of prestressing tendons and so on.The results show that:the serious quality problems such as disqualification of tensile strength,yield strength,weight and chemical compositions of prestressing tendons,and insufficient installation depth of the poles in the construction process gave rise to the fracture failure of the poles.关键词
钢筋混凝土/电杆/断裂/质量问题/埋深Key words
reinforced concrete/pole/fracture/quality problem/installation depth分类
建筑与水利引用本文复制引用
熊亮,万克洋,刘蛟蛟,曹智..钢筋混凝土电杆断裂原因分析[J].理化检验-物理分册,2017,53(11):826-828,3.