| 注册
首页|期刊导航|理化检验-物理分册|钢筋混凝土电杆断裂原因分析

钢筋混凝土电杆断裂原因分析

熊亮 万克洋 刘蛟蛟 曹智

理化检验-物理分册2017,Vol.53Issue(11):826-828,3.
理化检验-物理分册2017,Vol.53Issue(11):826-828,3.DOI:10.11973/lhjy-wl201711014

钢筋混凝土电杆断裂原因分析

Reason Analysis on Fracture of Reinforced Concrete Poles

熊亮 1万克洋 2刘蛟蛟 1曹智2

作者信息

  • 1. 国网湖南省电力公司电力科学研究院,长沙 410007
  • 2. 湖南省湘电锅炉压力容器检验中心有限公司,长沙 410004
  • 折叠

摘要

Abstract

Two reinforced concrete poles in one substation fractured and collapsed suddenly,causing damage to the transformer and related equipments.Fracture reasons of reinforced concrete poles were analyzed by macro observation,measurement of cobblestone diameter and dimension of spiral steel bars, weigh measurement, mechanical property testing,chemical composition analysis of prestressing tendons and so on.The results show that:the serious quality problems such as disqualification of tensile strength,yield strength,weight and chemical compositions of prestressing tendons,and insufficient installation depth of the poles in the construction process gave rise to the fracture failure of the poles.

关键词

钢筋混凝土/电杆/断裂/质量问题/埋深

Key words

reinforced concrete/pole/fracture/quality problem/installation depth

分类

建筑与水利

引用本文复制引用

熊亮,万克洋,刘蛟蛟,曹智..钢筋混凝土电杆断裂原因分析[J].理化检验-物理分册,2017,53(11):826-828,3.