摘要
Abstract
The electrical breakdown of camellia seed vegetable insulating oil and mineral insulating oil transformer is simulated in experiments,respectively.The dissolved gas characteristics of two kinds of insulating oil are studied by means of dissolved gas analysis method.The type and percentage of gas produced by oil paper breakdown of the two kinds of insulating oil are analyzed and compared.Results show that the two insulating oils produce seven characteristic gases,i.e.H2 ,CH4 ,C2 H4 ,C2 H6 ,C2 H2 ,CO and CO2 ,under the typical electrical faults.The total amount of gas produced in camellia-seed vegetable insulating oil increases with the increase of the times of breakdown,and the content of CO and CO2 produced by the insulating oil of camellia seed vegetable is greater than that of mineral insulating oil.The percentage of C2 H2 is always the highest,which shows that C2 H2 is the main characteristic gas of camellia seed vegetable insulating oil breakdown.关键词
植物绝缘油/变压器/击穿故障/溶解气体/产气含量Key words
vegetable insulating oil/transformer/breakdown discharge/dissolved gas/gas content分类
信息技术与安全科学引用本文复制引用
蔡胜伟,王飞鹏,陈程,范帆,陈江波,文刚,李剑,相晨萌,王吉..植物绝缘油击穿放电故障特征气体分析[J].重庆大学学报,2017,40(12):52-58,7.基金项目
国家电网公司科技项目(植物绝缘油变压器应用及运维关键技术研究).Supported by Science and Technology Proiect of SGCC(Research on application and operation of transformers immersed vegetable insulation oil ). (植物绝缘油变压器应用及运维关键技术研究)