基于母线划分的故障选线装置IEC 61850建模及功能实现
Modelling of IEC 61850 architecture based on bus partition and its implementation for single-line-to-ground fault line selection device
摘要
Abstract
The popularization and application of fault line selection ( FLS ) device in the smart substation is seriously hindered because the single-line-to-ground FLS information model is not clearly defined in IEC 61850 standard. Establishing the FLS intelligent electrical device( IED) model which meets the IEC 61850 standard is a critical mission in smart substation FLS IED development.The fault line selection function logical nodes based on bus partition are set up according to the functional features of FLS IED and the information model of IEC 61850 in this paper.The current logical nodes are extended, and the practical FLS device model is also obtained.Fault line selection in the smart substation is achieved by using the intelligent electronic device capability description( ICD) files of FLS IED which is developed on substation configuration language ( SCL) .FLS IED communication program is developed based on the MMS protocol stack.The communication function of FLS device is tested by using standardized IEDScout client software.Rationality of the FLS IED model and correctness of the communication function are finally verified in this paper.关键词
故障选线装置/IEC61850标准/电力通信模型/变电站配置语言Key words
fault line selection device/IEC 61850 standard/power communication model/substation configuration language分类
信息技术与安全科学引用本文复制引用
张孟琛,郑福亭,王福强,贾清泉,王锡魁..基于母线划分的故障选线装置IEC 61850建模及功能实现[J].燕山大学学报,2017,41(6):534-538,5.基金项目
国家自然科学基金资助项目(51477147) (51477147)