| 注册
首页|期刊导航|中国电力|换流站联络变充电励磁涌流对哈郑特高压直流运行影响分析

换流站联络变充电励磁涌流对哈郑特高压直流运行影响分析

郑彬 杨鹏 滕文涛 班连庚 项祖涛 吴娅妮 张媛媛 骆立实 潘一飞

中国电力2017,Vol.50Issue(12):130-135,6.
中国电力2017,Vol.50Issue(12):130-135,6.DOI:10.11930/j.issn.1004-9649.201608065

换流站联络变充电励磁涌流对哈郑特高压直流运行影响分析

Study on Influence of Coupling Transformer Charging Inrush Current to Hami-Zhengzhou UHV DC Project

郑彬 1杨鹏 2滕文涛 1班连庚 1项祖涛 1吴娅妮 1张媛媛 1骆立实 3潘一飞3

作者信息

  • 1. 电网安全与节能国家重点实验室(中国电力科学研究院),北京100192
  • 2. 中国电力技术装备有限公司,北京 100052
  • 3. 国网冀北电力公司,北京 100053
  • 折叠

摘要

Abstract

Inrush current during charging of coupling transformer in UHV DC converter station results in converter AC bus voltage distortion and harmonics in DC system.The harmonics are dominated by second and third order harmonic.Harmonic leads to DC voltage,current and power fluctuations and especially system overvoltage,which may result in DC power system harmonic protection alarm and even action in severe cases.It affects safe and stable operation of UHV DC project.Based on practical system condition,charging inrush current and vohage harmonic characteristics of two expansion groups of 750/500 kV coupling transformers in Tianshan converter station are studied.The influence on harmonic protection of Hami-Zhengzhou ±800 kV UHV DC project is investigated and suggestions on safety measures for coupling transformers energizing are proposed.The results provide effective countermeasures to ensure safe operation of Hami-Zhengzhou UHV DC project.These results also offer useful reference and guidance for other similar projects.

关键词

特高压直流/联络变/励磁涌流/谐波保护/对策措施

Key words

UHV DC project/coupling transformer/inrush current/harmonic protection/countermeasure

分类

信息技术与安全科学

引用本文复制引用

郑彬,杨鹏,滕文涛,班连庚,项祖涛,吴娅妮,张媛媛,骆立实,潘一飞..换流站联络变充电励磁涌流对哈郑特高压直流运行影响分析[J].中国电力,2017,50(12):130-135,6.

基金项目

国家电网公司科技项目(SGNX0000DKJS1500066)This work is supported by Science and Technology Project of State Grid Corporation of China (No.SGNX0000DKJS1500066). (SGNX0000DKJS1500066)