| 注册
首页|期刊导航|高压电器|环网柜电缆室电缆过长对套管受力分析

环网柜电缆室电缆过长对套管受力分析

方春华 潘明龙 易满成 顾春晖 李桂军 沈应涛

高压电器2018,Vol.54Issue(1):23-28,6.
高压电器2018,Vol.54Issue(1):23-28,6.DOI:10.13296/j.1001-1609.hva.2018.01.004

环网柜电缆室电缆过长对套管受力分析

Force Analysis of Casing Caused by Over-length Cable in Cable Room of Ring Network Cabinet

方春华 1潘明龙 1易满成 2顾春晖 2李桂军 3沈应涛3

作者信息

  • 1. 三峡大学电气与新能源学院,湖北宜昌443002
  • 2. 南网广州供电公司,广州510080
  • 3. 欧玛嘉宝(珠海)开关设备有限公司,广东珠海519070
  • 折叠

摘要

Abstract

SF6 European ring network cabinet is widely used in the domestic 10 kV distribution network nowadays,but when it is connected with the three-core cable,the casing is always damaged by the bending cable core wire,because the large stress is produced for bending of the overlong cable core wire.In this paper,the force to the casing generated by the different lengths and different types of cable core wire is simulated and analyzed based on Ansys finite element analysis software,and the simulation results is verified through the experimental.The results show that when the core wire is cut too long the force to casing decreased significantly with its height increased.After the test to determine the allowable loads(500 N) for the casing,ring network cabinet casing height should not be less than 800 mm.

关键词

环网柜/有限元/电缆终端/套管受力

Key words

ring network cabinet/finite element/cable terminal/casing stress

引用本文复制引用

方春华,潘明龙,易满成,顾春晖,李桂军,沈应涛..环网柜电缆室电缆过长对套管受力分析[J].高压电器,2018,54(1):23-28,6.

基金项目

特高压工程技术国家工程实验室开放基金 ()

三峡大学人才启动基金(KJ2014B054).Project Supported by National Laboratory Open Fonudation of UHV Engineering Technology Reserch,Foundation for Talents of Three Gorges University(KJ2014B054). (KJ2014B054)

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量0
|
下载量0
段落导航相关论文