±1100kV特高压直流换流站平抗分置特性仿真研究

刘士利 张力丹 胡劲松 胡楚芸 拾杨 龚树东 刘明岳

高压电器2018,Vol.54Issue(2):33-38,45,7.
高压电器2018,Vol.54Issue(2):33-38,45,7.DOI:10.13296/j.1001-1609.hva.2018.02.006

±1100kV特高压直流换流站平抗分置特性仿真研究

Simulation Research of the Characteristics of Separate Arrangement of Split Smoothing Reactor for ±1100 kV UHVDC Converter Station

刘士利 1张力丹 1胡劲松 2胡楚芸 1拾杨 2龚树东 3刘明岳3

作者信息

  • 1. 东北电力大学电气工程学院,吉林132012
  • 2. 国网北京经济技术研究院,北京102209
  • 3. 沈阳电力勘测设计院,沈阳110003
  • 折叠

摘要

Abstract

The insulation coordination of the UHVDC converter station plays an important role in the security and economic of UHVDC system.In this paper,we build the simulation model of the ± 1 100 kV UHVDC converter station based on PSCAD for the arrester configuration scheme of ±1 100 kV converter station.And using the system control parameter for reference,we simulate and analyze the effect of the different layout scheme of the smoothing reactor on the highest operating voltage in each key point of the converter valve system and analyze the voltage variation at valve-side on the highest converter transformer when happening grounding fault on the DC line.The results show that the highest operating voltage of the key position can be reduced by about 33 kV(3%)and the voltage variation of valve-side winding can be ruduced by about 60 kV by separating arrangement of split smoothing reactor,the simulation data is of reference significance to the overvoltage protection of ± 1 100 kV converter station.

关键词

换流站/避雷器/平抗分置/运行电压

Key words

converter station/arrester/separate arrangement of split smoothing reactor/operating voltage

引用本文复制引用

刘士利,张力丹,胡劲松,胡楚芸,拾杨,龚树东,刘明岳..±1100kV特高压直流换流站平抗分置特性仿真研究[J].高压电器,2018,54(2):33-38,45,7.

基金项目

东北电力大学博士科研启动基金项目(BSJXM201301).Project Supported by Doctoral Research Foundation of Northeast Electric Power University(BSJXM201301). (BSJXM201301)