人员活动和空气净化器对支气管镜室空气微生物和颗粒物的影响

安弘 高兴林 吴健 李琼 张莉滟 侯铁英 陈娉娉 何碧芳 黎秀玉 李东风

中国感染控制杂志2017,Vol.16Issue(12):1109-1115,7.
中国感染控制杂志2017,Vol.16Issue(12):1109-1115,7.DOI:10.3969/j.issn.1671-9638.2017.12.002

人员活动和空气净化器对支气管镜室空气微生物和颗粒物的影响

Effect of human activities and air purifier on airborne microorganisms and particulate matter in a bronchoscopy room

安弘 1高兴林 2吴健 1李琼 2张莉滟 1侯铁英 2陈娉娉 2何碧芳 2黎秀玉 2李东风2

作者信息

  • 1. 南方医科大学,广东广州510515
  • 2. 广东省人民医院广东省医学科学院广东省老年医学研究所,广东广州510080
  • 折叠

摘要

Abstract

Objective To evaluate the effect of personnel activities and air purifiers on airborne microorganisms and particulate matter in bronchoscopy room.Methods According to whether there was personal activity and air purifier in the bronchoscopy room,the experiment was divided into four groups:dynamic non-purification group,dynamic purification group,static non-purification group,and static purification group,indoor air samples were collected and analyzed at five different time points (0,0.5,1,2,4 h),microorganisms in the air were collected by planktonic method,then cultured and counted,concentration of particulate matter was determined by DT-9881M laser dust particle counter,variance analysis of factorial design was used for statistical analysis.Results Colony count/concentration of airborne bacteria,fungi,total microorganisms (bacteria + fungi),PM2.5,and PM2.5-10.0 in dynamic non purification group were (113.53 ± 7.78) CFU/m3,(89.67 ± 7.17) CFU/m3,(203.20 ± 10.92) CFU/m3,(86 557.20 ±4 158.29) counts/m3,and (659.69 ± 38.91) counts/m3 respectively,in static non-purification group were (84.33 ± 3.65) CFU/m3,(65.00 ± 2.65)CFU/m3,(149.33 ± 4.98) CFU/m3,(45 812.64 ±1 279.61) counts/m3,and (189.15 ± 4.64) counts/m3 respectively,in dynamic purification group were (84.80 ±8.08) CFU/m3,(90.40 ± 5.50) CFU/m3,(175.20 ± 9.22) CFU/m3,(49 336.38 ± 2 039.16) counts/m3,and (218.36 ± 7.02) counts/m3 respectively,in static purification group were (67.80 ± 5.63) CFU/m3,(38.27 ± 3.70)CFU/m3,(106.07 ± 6.76) CFU/m3,(29 772.53 ± 2 212.93) counts/m3,and (124.80 ± 7.16) counts/m3 respectively.Colony count/concentration of airborne bacteria,total microorganisms,PM2.5,and PM2.s 10.0 in dynamic group were all higher than those in static group,non-purification group were higher than purification group(both P <0.05),colony count of fungi in dynamic non-purification group was higher than static non-purification group,in static purification group was lower than static non-purification group(both P<0.05),there was no significant difference between dynamic purification group and dynamic non-purification group (P =0.936).Conclusion Personal activities can increase colony count/concentration of microorganisms and particulate matter in bronchoscopy room,air purifier can reduce the bacteria,total microbial count,and particulate matter in the air of bronchoscopy room.

关键词

支气管镜室/空气净化器/细菌/真菌/PM2.5/PM2.5~10.0

Key words

bronchoscopy room/air purifier/bacteria/fungus/PM2.5/PM2.5-10.0

分类

医药卫生

引用本文复制引用

安弘,高兴林,吴健,李琼,张莉滟,侯铁英,陈娉娉,何碧芳,黎秀玉,李东风..人员活动和空气净化器对支气管镜室空气微生物和颗粒物的影响[J].中国感染控制杂志,2017,16(12):1109-1115,7.

基金项目

广州市健康医疗协同创新重大专项基金(No.201400000002) (No.201400000002)

广东省科技计划项目(No.2013B031800026) (No.2013B031800026)

广州市科技计划项目(N0.2014J4100040) (N0.2014J4100040)

中国感染控制杂志

OA北大核心CSTPCD

1671-9638

访问量0
|
下载量0
段落导航相关论文