电力系统自动化2018,Vol.42Issue(6):33-39,91,8.DOI:10.7500/AEPS20170708001
含高比例光伏的配电网有功—无功功率多目标协调优化
Multi-objective Coordinated Optimization of Active and Reactive Power for Distribution Network Integrated with High Proportion of Photovoltaic Generation
郑能 1丁晓群 1郑程拓 1管志成 1蒋煜1
作者信息
- 1. 河海大学能源与电气学院,江苏省南京市210098
- 折叠
摘要
Abstract
High proportion of grid-connected photovoltaic system brings new problems and challenges to the optimization of active and reactive power in distribution networks.Therefore,a multi-obj ective coordinated optimization model of active and reactive power based on the mixed integer second order cone programming is proposed.Firstly,a mixed integer nonlinear programming problem is relaxed into a mixed integer second order cone programming problem by using the second order cone relaxation technique.Secondly,theε-constraint method is utilized to characterize the Pareto efficient frontier of multi-obj ective problem.Thirdly,this problem is decomposed into a linear programming master problem with 0-1 integer variables and a second order cone programming sub-problem with continuous variables by means of Benders decomposition method.Moreover, the master problem and sub-problem use Benders cut as a bridge to alternately iterate until the result converges to an optimal solution.Finally,the numerical simulation is performed in the improved IEEE 33-node distribution system,and the results show the effectiveness of the proposed model.关键词
光伏系统/二阶锥规划/有功—无功功率优化/多目标/Benders分解Key words
photovoltaic system/second order cone programming/optimization of active and reactive power/multi-objective/Benders decomposition引用本文复制引用
郑能,丁晓群,郑程拓,管志成,蒋煜..含高比例光伏的配电网有功—无功功率多目标协调优化[J].电力系统自动化,2018,42(6):33-39,91,8.