流体机械2018,Vol.46Issue(3):84-88,77,6.DOI:10.3969/j.issn.1005-0329.2018.03.017
两级转轮除湿空调系统性能的试验研究
Experimental Study on Performance of Two Stage Rotary Desiccant Air Conditioning System
摘要
Abstract
The effects of various factors on the air supply temperature and the cooling capacity of the two stage rotary desiccant air conditioning system were studied by the orthogonal experiment method.Experimental conditions is thatfresh air temperature value:27~33,air relative humidity value:50%~70%,regeneration air temperature of 55~75℃,regeneration air relative humidity:9%,inverter cold hot water pump set to 50 Hz.Results show,the effect of various factors on the air supply temperature is that relative humidity of fresh air inlet>fresh air inlet temperature> regeneration temperature,the effect of various factors on dehumidification capacity is that fresh air inlet temperature >relative humidity of fresh air inlet > regeneration temperature,the effect of various factors on the cooling capacity is that fresh air inlet temperature> regeneration temperature >relative humidity of fresh air inlet.关键词
转轮除湿/送风温度/制冷量Key words
rotary desiccant/air supply temperature/cooling capacity分类
机械制造引用本文复制引用
侯小兵,邹同华,代咪咪..两级转轮除湿空调系统性能的试验研究[J].流体机械,2018,46(3):84-88,77,6.基金项目
天津市应用基础与前沿技术研究计划重点项目(16JCZDJC31500) (16JCZDJC31500)