| 注册
首页|期刊导航|南方电网技术|±800 kV隔离开关地震模拟振动台试验研究

±800 kV隔离开关地震模拟振动台试验研究

文嘉意 谢强 胡蓉 孙帮新 卓然

南方电网技术2018,Vol.12Issue(1):14-20,7.
南方电网技术2018,Vol.12Issue(1):14-20,7.DOI:10.13648/j.cnki.issn1674-0629.2018.01.003

±800 kV隔离开关地震模拟振动台试验研究

Research of Seismic Simulation Test on Shaking Table of ± 800 kV Disconnect Switch

文嘉意 1谢强 1胡蓉 2孙帮新 2卓然3

作者信息

  • 1. 同济大学建筑工程系,上海200092
  • 2. 南方电网超高压输电公司,广州510620
  • 3. 直流输电技术国家重点实验室(南方电网科学研究院),广州510663
  • 折叠

摘要

Abstract

Seismic performance is meaningful for high voltage disconnect switch, which is vulnerable to the earthquake for its long span,great height,and flexibility. In this paper,a full-scale shake table test on 800 kV three-post disconnect switch is carried out to obtain its dynamical properties and seismic responses laws. The effect on disconnect switch's posts caused by the main blade is studied in different direction via characteristics of acceleration amplification factor and the spectrum analysis method. The results indicate the space lattice tilted structure form can limit the adverse impacts on seismic responses induced by the height and flexibility of the equip-ment. Meanwhile,after the main blade closed,a certain constraint effect will occur in the along-span direction, while in the across-span direction constraint effect is weak. The constraint effect can amplify and reduce the seismic responses of the post with blade and the post with fixed contact respectively.

关键词

隔离开关/振动台试验/地震响应/放大系数/约束效应

Key words

disconnect switch/shake table test/seismic responses/amplification factor/constraint effect

分类

信息技术与安全科学

引用本文复制引用

文嘉意,谢强,胡蓉,孙帮新,卓然..±800 kV隔离开关地震模拟振动台试验研究[J].南方电网技术,2018,12(1):14-20,7.

南方电网技术

OA北大核心CSCDCSTPCD

1674-0629

访问量0
|
下载量0
段落导航相关论文