| 注册
首页|期刊导航|中国电力|运行复合绝缘子界面问题分析

运行复合绝缘子界面问题分析

王康 朱亚洲 周辛南 吴照国 胡远翔

中国电力2018,Vol.51Issue(4):45-52,8.
中国电力2018,Vol.51Issue(4):45-52,8.DOI:10.11930/j.issn.1004-9649.201702040

运行复合绝缘子界面问题分析

Analysis on the Interfacial Issues of Running Composite Insulators

王康 1朱亚洲 2周辛南 1吴照国 3胡远翔1

作者信息

  • 1. 国网冀北电力有限公司电力科学研究院,北京 100045
  • 2. 国网冀北电力有限公司 张家口供电公司,河北 张家口 075000
  • 3. 国网重庆市电力公司电力科学研究院,重庆 401123
  • 折叠

摘要

Abstract

In order to study the interface problems of running composite insulator, 37, 68 and 38 composite insulators with different operating years are selected respectively from Guangdong, Guangxi and Hebei areas to test the performance of the interfaces between the core and sheds, between fittings, cores and sheds material, and between the housing and sheds. It is discovered by using the statistical analysis method that 50% of the early composite insulators have poor bondings between the housing and the core; the end fittings and sealants become invalid in various extents; 83.8% of samples from Guangdong area become invalid in the seal between the inside of fittings and tope of the core; 78% of the samples from Hebei and Guangxi areas are degraded. The composite insulators made by compression technology is poor in bonding between the housings and sheds and can be stripped easily by hand. Aimed at the poor sensitivity of the method defined in the standard to detect the interface performance, a new method is proposed to test the interface performance through detecting the variation of DC leakage current of samples before and after boiling.

关键词

复合绝缘子/界面性能/水煮试验/泄漏电流/检测方法

Key words

composite insulator/interface performance/boiling test/DC leakage current/testing method

分类

信息技术与安全科学

引用本文复制引用

王康,朱亚洲,周辛南,吴照国,胡远翔..运行复合绝缘子界面问题分析[J].中国电力,2018,51(4):45-52,8.

中国电力

OA北大核心CSCDCSTPCD

1004-9649

访问量0
|
下载量0
段落导航相关论文