南方电网技术2017,Vol.11Issue(12):9-15,22,8.DOI:10.13648/j.cnki.issn1674-0629.2017.12.002
特高压直流输电系统旁路断路器保护的改进和仿真
Improvement and Simulation of Bypass Circuit Breaker Protection for UHVDC Transmission System
严喜林 1邬乾晋 1国建宝 1王学之 1顾保全1
作者信息
- 1. 中国南方电网超高压输电公司检修试验中心,广州510663
- 折叠
摘要
Abstract
Combined with the principle of bypass switch protection stage 1 (82BPS-1),the action reason and existing risk of 82BPS-1 protection in Puer-Qiaoxiang UHVDC on September 10 of 2015 is analyzed.Then the defect of bypass switch protection is found that the unreasonable integral counting module can make 82BPS-1 protection maloperation.Aiming at the problem,an improved measure is proposed which using the bypass switch closing order to clear the count of 82BPS-1 protection integral counting module.The effective ness of the measure has been verified by RTDS simulation tests.At present,the improved measure has been applied to Puer-Qiaoxiang and Chuxiong-Suidong UHVDC transmission systems.关键词
特高压直流/旁路断路器保护/保护误动/控制保护系统Key words
UHVDC/bypass switch protection/protection maloperation/control and protection system分类
信息技术与安全科学引用本文复制引用
严喜林,邬乾晋,国建宝,王学之,顾保全..特高压直流输电系统旁路断路器保护的改进和仿真[J].南方电网技术,2017,11(12):9-15,22,8.