| 注册
首页|期刊导航|高压电器|固体绝缘环网柜开关模块局部放电原因分析及解决方案

固体绝缘环网柜开关模块局部放电原因分析及解决方案

刘玉春 董雪生 郎福成

高压电器2018,Vol.54Issue(8):246-251,6.
高压电器2018,Vol.54Issue(8):246-251,6.DOI:10.13296/j.1001-1609.hva.2018.08.039

固体绝缘环网柜开关模块局部放电原因分析及解决方案

Analysis of PD Causes and Solutions of Switch Module of SIRMU

刘玉春 1董雪生 1郎福成2

作者信息

  • 1. 上海雷博司电气股份有限公司,上海 201807
  • 2. 国网辽宁省电力有限公司电力科学研究院,沈阳 110006
  • 折叠

摘要

Abstract

The PD problem is one of the bottlenecks affecting the development and promotion of SIRMU. In order to solve the problem of PD of SIRMU, the reasons and the locations of the PD are analyzed in detail from the causes of PD and its classification, which is based on the structural characteristics of switch module. Some solutions of the PD problem are put forward by electric field analyzing and optimizing with the finite element software, which are solved by adding shields in key parts of switch module. The proposed solutions have completely solved the problem of PD of switch module, which are suitable for industrial production after verification.

关键词

固体绝缘环网柜/局部放电/开关模块/关键部位

Key words

solid-insulated ring main unit (SIRMU)/partial discharge/switch module/key parts

引用本文复制引用

刘玉春,董雪生,郎福成..固体绝缘环网柜开关模块局部放电原因分析及解决方案[J].高压电器,2018,54(8):246-251,6.

高压电器

OA北大核心CSCDCSTPCD

1001-1609

访问量1
|
下载量0
段落导航相关论文