| 注册
首页|期刊导航|家电科技|双生空调系统分歧管长度对室内机能力的影响分析

双生空调系统分歧管长度对室内机能力的影响分析

王永琳 胡英绪 蒋贤国 胡敬伟 张峥 刘玲

家电科技Issue(z1):57-60,4.
家电科技Issue(z1):57-60,4.DOI:10.19784/j.cnki.issn1672-0172.2023.99.014

双生空调系统分歧管长度对室内机能力的影响分析

Analysis of the influence of branch pipe length on indoor unit capacity in twin air conditioning systems

王永琳 1胡英绪 1蒋贤国 1胡敬伟 1张峥 1刘玲1

作者信息

  • 1. 海信家电集团股份有限公司 山东青岛 266000||海信空调有限公司 山东青岛 266000
  • 折叠

摘要

Abstract

The twin air conditioning system utilizes branch pipe components for mechanical flow separation,and the length of branch pipes connecting each indoor unit has a significant impact on the capacity of the indoor unit in that circuit.In order to ensure uniform distribution of refrigerant in each indoor unit and equivalent capacity output,theoretical analysis was conducted on the impact of branch pipe length on capacity,and experimental verification was conducted.Finally,it is suggested that the length difference of the split manifold during actual installation should be controlled within 8 m to ensure the stable operation of the twin air conditioning system.

关键词

双生空调系统/室内机能力/分歧管长度差

Key words

Twin air conditioning system/Indoor unit capacity/Difference in length of branch pipes

分类

通用工业技术

引用本文复制引用

王永琳,胡英绪,蒋贤国,胡敬伟,张峥,刘玲..双生空调系统分歧管长度对室内机能力的影响分析[J].家电科技,2023,(z1):57-60,4.

家电科技

1672-0172

访问量0
|
下载量0
段落导航相关论文