高比例新能源送端系统暂态电压运行风险分析

韩璐 尹纯亚 戴晨 马星

电力系统保护与控制2024,Vol.52Issue(1):23-34,12.
电力系统保护与控制2024,Vol.52Issue(1):23-34,12.DOI:10.19783/j.cnki.pspc.230311

高比例新能源送端系统暂态电压运行风险分析

Transient voltage operational risk of a high-proportion new energy sending system

韩璐 1尹纯亚 1戴晨 2马星3

作者信息

  • 1. 新疆大学电气工程学院,新疆 乌鲁木齐 830017
  • 2. 中电建湖北电力勘测设计院规划分院研究院,湖北 武汉 430000
  • 3. 国网新疆电力有限公司电力科学研究院,新疆 乌鲁木齐 830011
  • 折叠

摘要

Abstract

The transient voltage evolution and propagation and operational risk of a high-proportion new energy sending system in AC/DC faults are unclear.Thus,first,based on an analysis of the reactive voltage interaction mechanism between AC and DC systems,the characteristics and dominant influencing factors of transient voltage in AC and DC faults are identified,and the transient voltage evolution propagation path dominated by power electronic equipment in such a system is clarified.Second,the transient voltage operational risk is systematically considered from three aspects:the strong coupling effect of AC and DC faults continuing to strengthen,and the transient reactive power component is complex;the proportion of new energy continuing to increase,and the transient voltage problem becomes prominent;the tolerance for fault and adjustment ability decreases,and the risk of new energy tripping increases.Then,based on the DIgSILENT/PowerFactory,a simulation model of an actual high-proportion new energy multi-HVDC transmission system is established.The results with different new energy ratios and fault conditions verify the correctness of the transient voltage operational risk analysis.Finally,the technical prospect of coping with the operational risk of transient voltage is examined from the aspects of enhancing the mechanism understanding of coupling operational characteristics,improving the performance of a new energy-related grid,increasing the ability of multi-scale cooperative control strategy,and strengthening the AC grid structure.

关键词

高比例新能源送端系统/交直流故障/暂态电压/运行风险

Key words

high proportion new energy sending system/AC and DC faults/transient voltage/operation risk

引用本文复制引用

韩璐,尹纯亚,戴晨,马星..高比例新能源送端系统暂态电压运行风险分析[J].电力系统保护与控制,2024,52(1):23-34,12.

基金项目

国家自然科学基金项目资助(5236070148) This work is supported by the National Natural Science Foundation of China(No.5236070148). (5236070148)

电力系统保护与控制

OA北大核心CSTPCD

1674-3415

访问量0
|
下载量0
段落导航相关论文