节能2023,Vol.42Issue(12):8-11,4.DOI:10.3969/j.issn.1004-7948.2023.12.003
郑州市某园区地源热泵经济性能分析
Economic performance analysis of a ground source heat pump in a park in Zhengzhou City
摘要
Abstract
The screw chiller + boiler system in a park in Zhengzhou City was replaced with the ground source heat pump system of medium and deep groundwater + two-stage plate heat exchanger + double-effect heat pump unit,and the ground source heat pump system has good performance.The economics of the two systems were analyzed,and the initial investment cost and annual operating cost of the two systems were compared using the static payback period analysis method.The results show that the initial investment of the ground source heat pump system is 4.431 million yuan higher than that of the screw chiller + boiler system,and the annual operating cost is about 955 000 yuan lower than that of the screw chiller + boiler system,and the total investment amount of the screw chiller + boiler system after about 4.6 years can be equal to the total investment amount of the ground source heat pump system.The study indicates that in terms of long-term return on investment,compared with the screw chiller + boiler system,the ground source heat pump system has a higher economic value and is more energy-efficient.关键词
地源热泵系统/螺杆冷水机组+锅炉系统/初始投资费用/年运行费用/静态回收期Key words
ground source heat pump system/screw chiller + boiler system/initial investment cost/annual operating expenses/static payback period分类
建筑与水利引用本文复制引用
成天乐,姜曙,张垚,刘志明,赵朋朋,魏帅博,李欢凯,张毅豪..郑州市某园区地源热泵经济性能分析[J].节能,2023,42(12):8-11,4.基金项目
河南省2023年大学生创新创业训练计划国家级项目"对近零低能耗建筑在多重技术措施下的能量消耗探究"(项目编号:202311517008) (项目编号:202311517008)
河南工程学院横向科研项目(项目编号:HKJ2021024) (项目编号:HKJ2021024)