首页|期刊导航|电力系统自动化|面向系统功角稳定性提升的变速抽水蓄能机组故障穿越性能优化

面向系统功角稳定性提升的变速抽水蓄能机组故障穿越性能优化OA北大核心CSCDCSTPCD

Fault Ride-through Performance Optimization of Variable-speed Pumped Storage Units for Enhancing Power Angle Stability of Power Systems

中文摘要英文摘要

含定、变速机组的大容量抽水蓄能电站经弱交流通道送出场景下,定速机组存在功角失稳风险,为此,通过优化变速机组故障穿越性能提出了系统功角稳定性提升方法.首先,建立了抽水蓄能电站送出系统的动态模型,推导了变速机组输出功率对系统减速面积的灵敏度,明确了变速机组故障穿越特性对系统功角稳定的影响;然后,在确保故障期间变速机组转子无超速风险的前提下,提出了变速机组故障穿越电流限值和电压阈值的整定方法,以降低故障期间变速机组有功、无功功率恢复速度,提升系统功角稳…查看全部>>

In the scenario of large-capacity pumped storage power plant(PSPP)with fixed-speed pumped storage units(FSPSUs)and variable-speed pumped storage units(VSPSUs)transmitting through weak AC lines,there is a risk of power angle instability for the FSPSUs.Therefore,a method for improving system power angle stability is proposed by optimizing the fault ride-through(FRT)performance of VSPSUs.First,the dynamic model of the power transmission system of the PSPP is es…查看全部>>

陈骁;訾鹏;郝婧;刘瑛琳;赵峰;翟俊义

国家电网有限公司华北分部,北京市 100053国家电网有限公司华北分部,北京市 100053华北电力科学研究院有限责任公司,北京市 100045华北电力科学研究院有限责任公司,北京市 100045国家电网有限公司华北分部,北京市 100053中国石油大学(华东)新能源学院,山东省青岛市 266580

抽水蓄能机组故障穿越功角稳定电力系统

pumped storage unitfault ride-through(FRT)power angle stabilitypower system

《电力系统自动化》 2023 (24)

156-164,9

国家电网有限公司华北分部科技项目(52010123000M).This work is supported by North China Branch of State Grid Corporation of China(No.52010123000M).

10.7500/AEPS20230403006

评论

您当前未登录!去登录点击加载更多...