电气技术2024,Vol.25Issue(2):79-84,6.
制约葛南直流大负荷精准控制的关键因素
Key factors restricting accurate control of high load in Ge-Nan direct current project
付广旭 1王永平 1罗金辉1
作者信息
- 1. 南京南瑞继保电气有限公司,南京 211102
- 折叠
摘要
Abstract
In 2023,Ge-Nan DC project carried out the renovation of control,protection and converter valves.During the trial operation,there was an abnormal situation where the power did not reach 1 160MW due to overload limiting current.Therefore,the reason why the DC voltage at the sending end cannot reach the rated voltage during high load operation after the renovation of DC line is analyzed firstly.On this basis,the key factors restricting accurate control of high load are analyzed,including low AC voltage or low converter gear,higher relative DC inductive voltage drop set in the control than the actual value,and extinction angle operating above the rated reference value.Subsequently,a brief analysis is conducted on the impact of measurement error of DC voltage,deviation of DC line resistance and forward pressure drop of converter valve on accurate control of DC power.Finally,targeted solutions are proposed and validated through the real-time digital simulation platform.关键词
直流输电/精准控制/过负荷限制/大负荷/线路改造Key words
DC transmission/accurate control/overload limitation/high load/line renovation引用本文复制引用
付广旭,王永平,罗金辉..制约葛南直流大负荷精准控制的关键因素[J].电气技术,2024,25(2):79-84,6.