| 注册
首页|期刊导航|中国电机工程学报|高比例电力电子电力系统过电压(二):交流对称故障下暂时工频过电压机理

高比例电力电子电力系统过电压(二):交流对称故障下暂时工频过电压机理

徐式蕴 孙华东 王姝彦 王晶 毕经天

中国电机工程学报2024,Vol.44Issue(5):1701-1711,中插3,12.
中国电机工程学报2024,Vol.44Issue(5):1701-1711,中插3,12.DOI:10.13334/j.0258-8013.pcsee.222402

高比例电力电子电力系统过电压(二):交流对称故障下暂时工频过电压机理

Overvoltage of the Power System Integrated With High Proportion of Power Electronics Equipment(Ⅱ):Mechanistic Analysis of Transient Power Frequency Overvoltage Caused by AC Symmetrical Fault

徐式蕴 1孙华东 1王姝彦 1王晶 2毕经天1

作者信息

  • 1. 中国电力科学研究院有限公司,北京市 海淀区 100192
  • 2. 国家电力调度控制中心,北京市 西城区 100052
  • 折叠

摘要

Abstract

With the growing penetration of renewable energy sources,the problem of transient power frequency overvoltage caused by disturbance has become increasingly serious,which may lead to a large-scale off-grid accident of renewable energy sources and threat the operation of the grid.The low voltage ride through(LVRT)characteristics of the renewable energy sources directly affect the overvoltage level.There is an urgent need for in-depth research on overvoltage mechanism.This paper first analyzes the reason of overvoltage of high renewable penetration power system caused by AC symmetrical fault.Then a simplified model for analysis considering LVRT strategy of renewable energy sources is introduced.Further,after three-phase short-circuit fault clearance,the maximum overvoltage of the renewable energy source terminal is analyzed based on the vector relationship.Moreover,the influence of different LVRT strategy and system parameters on voltage rise is analyzed.Next,equivalent reactive current coefficient ranges avoiding off-grid accident are derived.Considering both reactive power support requirements of renewable energy during the fault and voltage safety constraints of renewable energy after fault clearance,the reasonable value ranges of the equivalent reactive current coefficient under different system strengths are analyzed.Finally,the time domain simulation is used to verify the validity of the theoretical analysis.

关键词

高比例电力电子电力系统/暂时工频过电压/机理分析/低电压穿越控制

Key words

power system integrated with high proportion of power electronics equipment/transient power frequency overvoltage/mechanistic analysis/low voltage ride through control

分类

信息技术与安全科学

引用本文复制引用

徐式蕴,孙华东,王姝彦,王晶,毕经天..高比例电力电子电力系统过电压(二):交流对称故障下暂时工频过电压机理[J].中国电机工程学报,2024,44(5):1701-1711,中插3,12.

基金项目

国家自然科学基金项目(51977197,U2166601,51907179). Program Supported by National Natural Science Foundation of China(51977197,U2166601,51907179). (51977197,U2166601,51907179)

中国电机工程学报

OA北大核心CSTPCD

0258-8013

访问量0
|
下载量0
段落导航相关论文