| 注册
首页|期刊导航|电工技术学报|基于谐波分量的配电电缆绝缘劣化状态带电检测技术

基于谐波分量的配电电缆绝缘劣化状态带电检测技术

徐海松 张大宁 胡冉 卢旭 王安哲 王昱力 张冠军

电工技术学报2024,Vol.39Issue(7):2161-2173,13.
电工技术学报2024,Vol.39Issue(7):2161-2173,13.DOI:10.19595/j.cnki.1000-6753.tces.231895

基于谐波分量的配电电缆绝缘劣化状态带电检测技术

A Live Detection Technology of Distribution Network Cable Insulation Deterioration State Based on Harmonic Components

徐海松 1张大宁 1胡冉 2卢旭 2王安哲 3王昱力 3张冠军1

作者信息

  • 1. 西安交通大学电气工程学院 西安 710049
  • 2. 深圳供电局有限公司 深圳 518000
  • 3. 中国电力科学研究院有限公司 武汉 430000
  • 折叠

摘要

Abstract

Due to restrictions imposed by power outages for maintenance on the urban power grid,the on-line detection technology of harmonic currents in distribution network cables is expected to become an effective supplement to traditional offline diagnostic methods,aiming to enhance the real-time diagnosis of the insulation status of distribution network cables. In this study,COMSOL finite element software was used to simulate the pores and water tree defects in the XLPE insulation layer of cables.The distribution of magnetic field strength in XLPE cables under different defect conditions was compared and analyzed.A real experimental platform for 10 kV distribution network cables was established,and typical defective cables with moisture and long-term thermal aging were prepared.The induced currents of aging defects and water tree defects in the XLPE cable insulation layer were collected in experiments,and the 2nd to 11th harmonic currents under different insulation defects were extracted.The influence patterns of pore depth caused by aging and external moisture intrusion on induced currents were obtained. To effectively assess the degree of cable degradation,a cable degradation assessment method based on the harmonic features of induced currents was constructed using LASSO regression.In the prediction analysis of normal thermally aged cables,the root mean square error of LASSO regression was 17.1 days,accounting for 14% of the actual aging time range,indicating high accuracy.The prediction of aging time for moisture-affected cables was longer,consistent with the actual state of accelerated insulation aging due to moisture. To accurately identify the type of insulation layer defects in cables,a defect identification method combining principal component analysis and clustering algorithm was developed based on the data sample set.When using harmonic data of a 300 A test current for clustering identification of moisture-affected and normal aging cables,the accuracy reached 75.64% ,effectively distinguishing between moisture-affected cables and normal cables. The cable insulation live diagnosis technology proposed in this study,based on the harmonic current characteristics,integrates cable insulation degradation status,induced harmonic current features,and clustering analysis algorithms,achieving intelligent identification of cable insulation defects.

关键词

感应电流谐波/XLPE劣化/LASSO回归分析/期望最大化聚类分析/绝缘状态评估

Key words

Inductive current harmonics/XLPE deterioration/LASSO regression analysis/expectation-maximization clustering analysis/insulation state assessment

分类

信息技术与安全科学

引用本文复制引用

徐海松,张大宁,胡冉,卢旭,王安哲,王昱力,张冠军..基于谐波分量的配电电缆绝缘劣化状态带电检测技术[J].电工技术学报,2024,39(7):2161-2173,13.

基金项目

深圳供电局有限公司科技项目资助(090000KK52220013). (090000KK52220013)