Abstract
The analysis and treatment of abnormal ultrasonic wave in the disconnecting switch(DS)compartment of PT of 110 kV GIS is introduced.It is judged through amplitude location,time delay location and the change of equip-ment operation state that the defect is from the inside of the DS compartment.Multiple kinds of spectrum analysis on the partial discharge ultrasonic signal are performed,thinking that the free metal particle at the bottom the compart-ment is the main reason which causes abnormal ultra sonic wave signal.It is found by opening the enclosure that the grading cover of the stationary contact of the blade has obvious scratches and many black solid debris are at the bot-tom of the gas compartment.The weak installation process of the blade causes the metal debris to drop at the bottom of the gas compartment,generating partial discharge and causing the ultrasonic wave signal abnormal.The discharge of disconnecting switch of PT is a typical metal particle discharge case,which has provided experience and reference for the analysis of the similar abnormal situation in the future.关键词
GIS设备/自由金属颗粒放电/异常超声波/开关Key words
GIS equipment/free metal particle discharge/abnormal ultrasonic wave/DS引用本文复制引用