电气技术2024,Vol.25Issue(4):72-76,5.
10kV箱变改造为发电机转子护环感应加热电源的研究与应用
Research and application of transforming 10kV box-type substation into induction heating power source for generator rotor retaining ring
申雁鹏 1王声学1
作者信息
- 1. 江苏核电有限公司,江苏 连云港 222042
- 折叠
摘要
Abstract
When the rotor of a turbine generator in a nuclear power plant is repaired for the first time and insulation defects occur in the winding,the rotor retaining ring should be removed by induction heating method for inspection and treatment.According to the actual situation of the power station and the demand of the retaining ring disassembly,after analysis and calculation,this paper uses the 10kV box-type substation decommissioned during the construction period as the induction heating power supply for generator rotor retaining ring according to the optimal single-winding power supply scheme,and it has been successfully applied in the first overhaul of two million-kilowatt turbogenerators and the treatment of rotor insulation defects,which effectively guarantees the overhaul period of nuclear power plant generators and saves the overhaul cost.关键词
箱式变电站/发电机/护环/感应加热Key words
box-type substation/generator/retaining ring/induction heating引用本文复制引用
申雁鹏,王声学..10kV箱变改造为发电机转子护环感应加热电源的研究与应用[J].电气技术,2024,25(4):72-76,5.