Study on the characteristics of indoor pollutant distribution in negative pressure wards under different air conditioning modes

中文摘要英文摘要

针对分体空调器、风机盘管都存在室内空气循环流动、冷凝水聚集等问题,本研究通过CFD软件对负压病房进行模拟,对比分析了辐射空调系统和风机盘管系统在负压病房应用时室内热湿环境、污染物分布特性和医护人员感染风险,并建立了全尺寸辐射空调负压病房实验室并对结果进行了验证.结果表明:采用辐射空调系统不仅能够降低室内垂直温差,减少吹风感,而且能够降低室内污染物浓度和室内人员感染风险;辐射空调与风机盘管相比室内污染物浓度、暴露风险和感染概率最大降幅分别为29.85%,29.27%和15.79%.研究结果可为负压病房的设计和医护人员感染风险评估提供参考.

In order to solve the problems of presence of indoor air circulation flow and condensate collection in both split air conditioners and fan coils,the negative-pressure wards were simulated using the CFD software,and the indoor heat and humidity environments,the characteristics of contaminant distribution,and the risk of infection for healthcare workers were compared and analyzed when radiant air conditioning systems and fan coil systems were applied in the negative-pressure wards,and a full-scale radiation air conditioning negative pressure ward laboratory was established to verify the results.The results show that the use of radiant air conditioning system can not only reduce the vertical temperature difference in the room and reduce the sense of blowing air,but also reduce the concentration of indoor pollutants and the risk of infection of indoor personnel.The maximum reductions in indoor pollutant concentration,exposure risk and probability of infection were 29.85%,29.27%and 15.79%for radiant air conditioning compared to fan coils,respectively.The results of the study can provide reference for the design of negative pressure wards and infection risk assessment for healthcare workers.

周崇钢;丁云飞;叶立飞

广州大学 土木工程学院,广州 510006

机械工程

负压病房辐射空调风机盘管污染物分布感染风险

negative pressure wardradiation air conditioningfan coilpollutant distributionrisk of infection

《流体机械》 2024 (004)

42-49,104 / 9

广州市科技计划重点项目(202206010132)

10.3969/j.issn.1005-0329.2024.04.007

评论