流体机械2024,Vol.52Issue(4):42-49,104,9.DOI:10.3969/j.issn.1005-0329.2024.04.007
不同空调模式下负压病房内污染物分布特性研究
Study on the characteristics of indoor pollutant distribution in negative pressure wards under different air conditioning modes
摘要
Abstract
In order to solve the problems of presence of indoor air circulation flow and condensate collection in both split air conditioners and fan coils,the negative-pressure wards were simulated using the CFD software,and the indoor heat and humidity environments,the characteristics of contaminant distribution,and the risk of infection for healthcare workers were compared and analyzed when radiant air conditioning systems and fan coil systems were applied in the negative-pressure wards,and a full-scale radiation air conditioning negative pressure ward laboratory was established to verify the results.The results show that the use of radiant air conditioning system can not only reduce the vertical temperature difference in the room and reduce the sense of blowing air,but also reduce the concentration of indoor pollutants and the risk of infection of indoor personnel.The maximum reductions in indoor pollutant concentration,exposure risk and probability of infection were 29.85%,29.27%and 15.79%for radiant air conditioning compared to fan coils,respectively.The results of the study can provide reference for the design of negative pressure wards and infection risk assessment for healthcare workers.关键词
负压病房/辐射空调/风机盘管/污染物分布/感染风险Key words
negative pressure ward/radiation air conditioning/fan coil/pollutant distribution/risk of infection分类
机械制造引用本文复制引用
周崇钢,丁云飞,叶立飞..不同空调模式下负压病房内污染物分布特性研究[J].流体机械,2024,52(4):42-49,104,9.基金项目
广州市科技计划重点项目(202206010132) (202206010132)