制冷2024,Vol.43Issue(2):8-12,5.DOI:10.3969/J.ISSN.1005-9180.2024.02.0002
苏州地铁车站冷水机组的NPLV研究与实践
Research and Practice on NPLV of Chiller Units in Suzhou Metro Station
史一锋 1徐保虎 2冯刚 2秦旭 3唐圆晨 3陆召伟4
作者信息
- 2. 苏州市轨道交通集团有限公司,苏州,215004
- 3. 广州地铁设计研究院股份有限公司,广州,510010
- 4. 广东美的暖通设备有限公司,佛山,510320
- 折叠
摘要
Abstract
Due to the significant difference in load characteristics between civil buildings and subway stations,and the value of the national standard IPLV is determined based on the composite distribution characteristics of civil buildings,the reflected load distribution,weight coefficients,and average cooling water inlet temperature differ greatly from subway engineering.Therefore,it is necessary to establish an NPLV that matches the load characteristics of different regions.This article establishes a calculation formula for the NPLV of Suzhou Metro based on the existing operational data of Suzhou Metro stations;A comparative analysis was conducted on the NPLV of Suzhou Metro in the near and long term;Preliminary exploration was conducted on the reference significance of NPLV for the selection of refrigeration units.关键词
NPLV/IPLV/地铁站/冷水机组/选型Key words
NPLV/IPLV/Subway stations/Refrigeration Units/Selection分类
建筑与水利引用本文复制引用
史一锋,徐保虎,冯刚,秦旭,唐圆晨,陆召伟..苏州地铁车站冷水机组的NPLV研究与实践[J].制冷,2024,43(2):8-12,5.