摘要

Abstract

Data center computer room air-conditioning equipment operates for prolonged periods,and its performance must be tested and evaluated annually to ensure safe and efficient operation.This study conducts field measurements on the server layout,blind plate structure,and working condition adaptability in the rack.The thermal environment of a data center using the closed cold aisle underfloor air distribution system is studied,and the thermal environment safety and energy efficiency throughout the year are evaluated through thermal performance indicators and energy efficiency indicators.The results show that it is recommended to install a rack with a power of more than 2 kW in the middle area of the cold aisle.Installing a blind plate in the gap between the racks can promote the circulation of cold air inside the server,reduce the backflow interference of hot air,and reduce the maximum outlet temperature by 3.32℃.The average supply air speed was reduced by approximately 24%.Under summer operating conditions,the PUE,WUE,and CUE of the data center were approximately 1.2,3.5,and 0.84,respectively,and the WUE exhibited strong seasonality.Under winter operating conditions,free cooling can effectively reduce the energy consumption of data centers.In addition,the overheating problem of the racks at the end of the cold aisle of the data center is significant.The cabinet cooling index of the 16 racks was less than 90%,and the heat loss was high.

关键词

数据中心/送风方式/机房空调/热性能评价指标/能源效率

Key words

data center/air supply scheme/computer room air conditioning/thermal performance evaluation index/energy efficiency

分类

通用工业技术

引用本文复制引用

高启明,张羽,冯秀敏,张忠斌..基于盲板的地板送风式数据中心热管理与能效案例研究[J].制冷学报,2024,45(3):129-142,14.

制冷学报

OA北大核心CSTPCD

0253-4339

访问量0
|
下载量0
段落导航相关论文